INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 15 of 21
fcd-dp_mi-r2.doc –
r.2
Proceed as follows to modify :
1. push the button
ESC
2. push several times the button until the pointer > points "set param"
3. push the button
OK
.
4. push several times the button until the display shows the parameter where to make the
modification (B3 - 1 or other)
5. push the button
OK
, the blinking cursor will take place on the line of the days (D)
6. by pushing the button the cursor moves on the positions correspondent to the days of
the week
7. push the button to enable/disable
8. by pushing the button the cursor moves on the several digits of the hours (lines ON and
OFF)
9. when the cursor blinks on the digit to modify, push several times the until the desired
number appears
10. repeat the same operations with other digits, whether required.
11. push the button
OK
to confirm the modifications
12. push the button to visualize other parameters which must be modified, and operate as
explained at above points 5 ÷11, or push the button
ESC
to leave the modification menu
13. push the button
ESC
to go back to visualization of service.
7.3. How to set time of phases, delay, pressure drop value
Proceed as follows to modify :
1. push the button
ESC
2. push several times the button until the pointed > points "set param"
3. push the button
OK
.
4. push several times the button until the parameter to modify is shown (B1 or other)
5. push the button
OK
.
6. by pushing the button , move the cursor on the digit to modify
7. when the cursor blinks on the digit to modify, push the button until thge desired digit
appears
8. repeat the same operations with other digits, whether required
9. push the button
OK
to confirm the modifications
10. proceed as explained for other modifications of other parameter or push the
ESC
per to
leave the modification menu
11. push the button
ESC
to go back to visualization of service
NOTE:
•
during the modifications, the normal service is NOT interrupted.
•
In modification menù, ref. to the timers, the digits visualized on the line (marked
as Ta) underneath the line of the time setting (marked as T), indicate the status
of the present counting of the time related to the selected timer
•
time basis are :
s = seconds (00,00 ÷ 99,95)
m = minutes (00:00 ÷ 99m:59s)
h = hours (00:00 ÷ 99h:59m)
•
although the programmer allows to set values up to 19999, in the field of the
max allowable pressure drop (B5), let us remind that the real max allowable
value is 100, correspondent to a pressure drop of 1 bar (=100 kPa = max
allowable value pressure drop across the filter).