![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/9/46/9465ef47-0925-4408-94ac-5a9a4c353fdf/9465ef47-0925-4408-94ac-5a9a4c353fdf-bg4.png)
Installation Guide
4
69-2609EFS—03
ENGLISH
Wiring
2H/1C Heat
Pump System
TH2210DH/TH1210DH
B Changeovervalveenergizedin
heating[5]
O Changeovervalveenergizedin
cooling[5]
G Fanrelay
Y Compressor contactor
Aux/E Auxiliaryheatrelay
C 24Vaccommon[3]
R Power[1]
1H/1C System
TH2110DH/
TH1110DH
(1 transformer)
G Fanrelay
Y Compressor contactor
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
1H/1C System
TH2110DH/
TH1110DH
(2 transformers)
G Fanrelay
Y Compressor contactor
W Heat relay
C 24Vaccommon[3,4]
R Power(heatingtransformer)[1,2]
Rc Power(coolingtransformer)[1,2]
Heat Only System
TH1100DH
W Heat relay
C 24Vaccommon[3]
R Power[1]
1H/1C Heat
Pump System
TH2110DH/TH1110DH [7]
B Changeovervalveenergizedin
heating[5]
O Changeovervalveenergizedin
cooling[5]
G Fanrelay
Y Compressorcontactor[6]
W [W+Yjoinedbyjumper]
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Heat Only
System
TH2110DH/TH1110DH
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Heat Only
System with
Fan TH2110DH/TH1110DH
G Fanrelay
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Cool Only
System
TH2110DH/TH1110DH
G Fanrelay
Y Compressor contactor
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
NOTES
Wirespecifications:
Use18-to22-gaugethermostatwire.
Shieldedcableisnotrequired.
[1] Powersupply.Providedisconnectmeans
andoverloadprotectionasrequired.
[2] Removejumperfor2-transformersystems.
[3] Optional24Vaccommonconnection.
[4] Commonconnectionmustcomefrom
coolingtransformer.
[5] UseeitherOorBterminalsforchangeover
valve.
[6] Useasmallpieceofwire(notsupplied)to
connectWandYterminals.
[7] SetfanoperationswitchtoHeat Pump
(seepage5).
Wiring guide — conventional and heat pump systems
CYGO
Aux/
E
M32809
Not
Used
RcCYW
M32811
RcCYW
M32812
RcCYWGO
M32813
RcC
M32814
RcCW
M32815
RcCY
M32816
See[notes]below
M32817
RW C
Not
Used