Central Station Communications Read Status
154 MS-9200UDLS PN 52750:A 11/04/05
The control panel is capable of reporting detailed messages depending upon the format
in use. Table 5.1 shows the reporting structure for all formats.
Refer to Table 5.2 for an explanation of each letter code in Table 5.1 . Refer to Table
5.3 for a list of compatible receivers.
Table 5.1 Format Selection
Format Format Format Format
Report 3+1/4+1/Standard
4+1 Express
3+1/4+1/Expanded 4+2/Standard
4+2 Express
4+2/Expanded
Alarm SSS(S) A SSS(S) A
AAA(A) Z
SSSS AA2 SSSS AZ
Alarm Restore SSS(S) RA SSS(S) RA
RARARA(RA) Z
SSSS RARA2 SSSS RAZ
Zone Trouble
(Zone Open)
SSS(S) TZ SSS(S) TZ
TZTZTZ(TZ) Z
SSSS TZTZ2 SSSS TZZ
Zone Trouble Restore SSS(S) RTZ SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSSS RTZRTZ2 SSSS RTZZ
System Trouble SSS(S) TS SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2 SSSS TSY
System Trouble Restore SSS(S) RTS SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2 SSSS RTSY
Zone Disable SSS(S) DZ SSS(S) DZ
DZDZDZ(DZ) Z
SSSS DZDZ2 SSSS DZZ
Zone Disable Restore SSS(S) RDZ SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
SSSS RDZRDZ2 SSSS RDZZ
Low Battery SSS(S) L SSS(S) L
LLL(L) L2
SSSS LL2 SSSS LL2
Low Battery Restore SSS(S) RL SSS(S) RL
RLRLRL(RL) RL2
SSSS RLRL2 SSSS RLRL2
AC Loss SSS(S) P SSS(S) P
PPP(P) P2
SSSS PP2 SSSS PP2
AC Loss Restore SSS(S) RP SSS(S) RP
RPRPRP(RP) RP2
SSSS RPRP2 SSSS RPRP2
Fire Drill SSS(S) FD SSS(S) FD
FDFDFD(FD) FD2
SSSS FDFD2 SSSS FDFD2
Fire Drill Restore SSS(S) RFD SSS(S) RFD
RFDRFDRFD(RFD) RFD2
SSSS RFDRFD2 SSSS RFDRFD2
Supervisory Condition SSS(S) V SSS(S) V
VVV(V) Z
SSSS VV2 SSSS VZ
Supervisory Condition
Restore
SSS(S) RV SSS(S) RV
RVRVRV(RV) Z
SSSS RVRV2 SSSS RVZ
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Upload or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2