Option 27 — Maximum Heating Setpoint
This selection a llows the installer to c onfigure the maximum heating setpoint.
The range is based on the adjustable deadband value Option 11, such that the
minimum of the range is 50_F and the maximum is 90_F minus the deadband.
Default is 88_F (based on the adjustable deadband default = 2).
Option 28 — UV Light Reminder
This selection allows the installer to select the number of months after which the
UV Light icon will be displayed to indicate to the homeowner that it is time to
call the dealer to have the UV Lights replaced. Selections available are OF (off),
6, 12, 18, 24, 30, 36, 42, 48.
OF (off) — The UV Light reminder is turned off and will never be displayed.
6-- 48 The number of months after which the UV Light reminder will be
displayed, “CHECK UV LIGHT”.
Default is OF (of f).
Option 29 — Humidifier Pad Reminder
This selects the number of months after which the Humidifier Pad Reminder
icon will be displayed. This is not based on run time.
OF (off) The Humidifier Pad Reminder is disabled and will never be
displayed.
1-- 24 The number of months after which the Humidifier Pad Reminder icon
will be displayed, “CHECK HUM PAD”.
Default is OF (of f).