Table 44—EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Enthalpy* Compressor NTerminal†
eman
ontro
Y1 Y2
Stage Stage
Occupied Unoccupied
entilation (DC
)
ut
oor
eturn
1 2
Damper
Below set
High
Low
On On On On
Minimum position Closed
(DCV LED Off)
(F ree Cooling LED Off)
On Off On Off
Off Off Off Off
Low
High
On On On Off
Modulating** (between min.
Modulating** (between
(F ree Cooling LED On)
On Off Off Off
position and full-open)
closed and full- open)
Off Off Off Off Minimum position Closed
Above set
High
Low
On On On On
Modulating†† (between min.
Modulating†† (between
(DCV LED On)
(F ree Cooling LED Off)
On Off On Off
position and DCV maximum)
closed and DCV
Off Off Off Off
ma
imum)
Low
High
On On On Off
Modulating*** Modulating†††
(F ree Cooling LED On)
On Off Off Off
Off Off Off Off
*Forsingleenthalpycontrol,themodulecomparesoutdoorenthalpyto theABCDsetpoint.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is basedon the supply-air sensor signal.
††Modulation is basedon the DCV signal.
***Modulationisbased on thegreater ofDCV andsupply-air sensor signals,between minimumposition andeither maximum position (DCV)or fully open (sup-
ply-air signal).
†††Modulationisbased on thegreater ofDCV andsupply-air sensor signals,between closedand either maximum position (DCV)or fully open(supply-airsig-
nal).
C06053
Fig. 67 --- EconoMi$er IV Functional View
581B,C