26 Instruction manual TWI 35-130 G/TWI 45-190 G
Speci cation of concentric roof ue terminal C33
3.9.4 Parallel connections
The table gives the maximum pipe length for parallel systems. The maximum
pipe length depends on the selected diameter.
Warning
Mount ue gas discharge material with a fall of 5 mm per metre towards
the device.
Requirements for ue gas discharge for parallel systems
Use the longest pipe for calculating the pipe length. If, for example, the ue gas
discharge pipe is 10 metres and the air supply pipe is 15 metres, use the 15
metres for calculating the length. Then add the Lequivalent to these 15 metres
for each 90° and 45° bend in both the air supply and the ue gas discharge. All
this will be explained using a practical example.
Practical example of parallel ue gas discharge
Example
The gure shows a TWI 35-130. The device is to be provided with a 25 m
parallel pipe with a diameter of 100 mm and eight 90° bends. An inspection
shall be carried out for compliance of the con guration with the requirements
stated in the table.
3
Installation
Subject Description
Roof ue terminal set:- 1x Roof ue
terminal (incl. clamping strip)
- 1x Pipe 1000 mm
- 1x Mounting ange
Item no.: TWI 35-130: 0305 042
(1)
TWI 45-190: 0305 042
(1)
Construction: Concentrique
Manufacturer: Muelink & Grol
Type : M2000 DDV HR-C
Piping material Construction : Concentrique
Flue gas discharge: Thick-walled aluminium with lip-ring sealing
Air supply: Thin-wall galvanised sheet steel
Pipe diameters Flue gas discharge: TWI 35-130: Ø 80 mm
TWI 45-190: Ø 80 mm
Air supply: TWI 35-130: Ø 125 mm
TWI 45-190:Ø 125 mm
(1) It is not allowed to use any other roof ue terminal. You can order the roof ue terminal mentioning the item
number with A.O. Smith, manufacturer or wholesaler’s.
Device Diameter
(1)
Maximum running length L
equivalent
90° bend
L
equivalent
45° bend
TWI 35-130 80 30 3,9 1,1
TWI 45-190 80 20 3,9 1,1
TWI 35-130 100 100 4,6 1,2
TWI 45-190 100 75 4,6 1,2
(1) The given larger diameter can be used if the maximum running length is insuf cient. When using a larger
diameter, this shall be used for both the air supply and the ue gas discharge.