Instruction manual GWV 33
is
Specification of condensation outlet for uninsulated lengths greater than 8
metres and no more than 20 metres
3.10 Electrical
connection
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations (1.3 "Regulations").
3.10.1 Introduction
Topics covered in this paragraph, in sequence:
Preparation;
Connecting the mains voltage;
A program-controlled pump, and external on/off switch and an alarm can
optionally be fitted to the appliance. For these options, see:
Connecting a program-controlled pump;
Connecting an external on/off switch;
Connecting an alarm signal ('Alarm OUT');
Sensor wiring
Note
The optional components are not included in the rating for electrical power
consumption stated in the table (3.4.2 "General and electrical specifications").
3.10.2 Preparation
Caution
The appliance is phase-sensitive. It is absolutely essential to connect the
mains live (L) to the live of the appliance, and the mains neutral (N) to the neutral
of the appliance.
The figure shows a view of the electrical connector block, and the table shows
the appropriate connections.
Subject Description
Condensation outlet set
1x clamping ring
•1x trap
2x pipe Ø 32x500 mm
2x bend, Ø 32 90
o
Item No. GWV 120: 0308 278
GWV 150: 0308 278
GWV 200: 0308 279
Construction n/a
Manufacturer Muelink & Grol
Type n/a
Pipe material Construction Parallel
Outlet Thick-walled aluminium with lipped sealing ring
Pipe diameters Outlet GWV 120: Ø 150 mm
GWV 150: Ø 150 mm
GWV 200: Ø 200 mm