Publication 1794-6.5.12 - September 2011
34 Read and Write Configuration Maps for the FLEX I/O Module
Word Dec. Bits
(Octal Bits)
Description
Read Word 10 00…07 Extended data table data response bits – These
bits echo the EDT command data written to the
module during calibration.
08…14
(10…16)
Extended data table command response bits
These bits echo the EDT command written to the
module during calibration.
15 (17) Reserved for factory use
Bit/Word Descriptions for Block Transfer Write Words
Word Dec. Bits
(Octal Bits)
Description
Write Word 0 00…02 Input Filter Selection bits
Bit 02 01 00 Filter Time Constants – actual filtering depends on the module mode of
operation
0 0 0 Hardware filtering only (default filtering)
0 0 1 25 ms
0 1 0 100 ms
0 1 1 250 ms
1 0 0 500 ms
1011s
1102 s
1115 s
Bits 03…05 Reference Junction – used when input type is set to thermocouple and sensor mode is set to
internal compensation. Sets a fixed reference junction to compensate all thermocouple channels.
Bit 05 04 03 Reference Junction
0 0 0 0 °C (32 °F)
0 0 1 20 °C (68 °F)
0 1 0 25 °C (77 °F)
0 1 1 30 °C (86 °F)
1 0 0 40 °C (104 °F)
1 0 1 50 °C (122 °F)
1 1 0 60 °C (140 °F)
1 1 1 70 °C (158 °F)
Bits 06…07 Fault Mode bits – when a bit is set (1), fault mode is enabled for that channel. Bit 06 corresponds to
channels 0…3; bit 07 corresponds to channels 4…7.
0 = Disabled
1 = Enable wire-off detection
Bits 08…11
(10…13)
Data format – module defaults to -4000…10000 in millivolt mode, and 0…5000 in
Ω mode with
implied decimal points (i.e. -40.00mV, 0.1 Ω) whenever °C, °F, °K is selected.