64 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Operation
The KYZ output can operate in any of the following modes:
Energy pulse operation with fixed pulse width or toggle
Forced operation
Setup
KYZ-output set-up parameters are found in the Advanced Setup menu and are summarized in
the table.
Commands
Force KYZ Output On
Force KYZ Output Off
Remove Force from KYZ
Related Functions
Configuration lock
Parameter Description Range Default User
Setting
Model
TR
1
TR
2
E
M
1
E
M
2
E
M
3
KYZ Output
Parameter
0 = Disable
1 = Wh Fwd
2 = Wh Rev
0…2 0
•••
3 = VARh Fwd
4 = VARh Rev
5 = VAh
0…5 ••
KYZ Output Scale The increase in value of the
selected parameter that caused
the output to change state
1…
100,000
1000 •••
KYZ Pulse
Duration Setting
0 = toggle output
50…1000 = duration of output
pulse, rounded to 10 ms
0 or 50…
1000
250 ms •••