Carrier TP-NRH-A Thermometer User Manual


 
31
Option 11 — Deadband Setting Between Heat & Cool
This option is not available on Heat Only and Cool Only systems. The selection
allows the installer to choose how much differential exists between the heating
and cooling setpoints. Allowable selections are 1 thru 6.
Default is 2.
Option 12 — Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery
time. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is
programmed. Not available with nonprogrammable Thermidistat Controls or
when Thermidistat Control is configured as nonprogrammable.
Default is 90.
Option 13 — Room Air Temperature Offset Adjust
The number of degrees to be added to the displayed temperature to calibrate or
deliberately miscalibrate the measured room temperature ( 5 to +5_).
Default is 0.
Option 14 — Humidity Display Offset Adjust
The percentage to be added to the displayed humidity to calibrate or deliberately
miscalibrate the measured room humidity (9% to +9% RH).
Default is 0.
Option 15 — Enable Auto Mode
This selection is not available if the Thermidistat Control is configured as Heat
Only or Cool Only in Option 1. This allows the homeowner to select auto
changeover mode in addition to heat and cool. This allows the Thermidistat